Field Wiring Connections

Make sure electrical power to the heater is discon-

nected to avoid potential serious injury or damage to

components.

CAUTION: Label all wires prior to disconnection

when servicing controls. Wiring errors can cause im-

proper and dangerous operation. Verify proper

operation after servicing.

DANGER: SHOCK HAZARD

Fig. 14: Rear Wiring Location

Fig. 16: XFyre Single Heater Control

DIMPLES FOR
ALTERNATE
LOW VOLTAGE
WIRE ROUTING

FIELD
WIRING
BOARD

Fig. 15: Front Wiring Location

Wiring the Thermostat

1. Connect the room thermostat to the terminals

marked THERMOSTAT in the electrical junction

box (shown in Fig. 16). Alternately, any dry contact

closure across these terminals will enable the

XFyre unit to run. Caution should be used to

ensure neither of the terminals becomes connect-

ed to ground.

2. Mount the thermostat on an inside wall as central

as possible to the area being heated, but away

from drafts or heat producing devices, such as tel-

evision sets, that could effect the ability of the

thermostat to measure the room temperature

accurately.

3. If the thermostat is equipped with an anticipator,

and it is connected directly to the XFyre boiler, the

anticipator should be set at .1 amps. If the thermo-

stat is connected to other devices, the anticipator

should be set to match the power requirements of

the device it is connected to. See the instruction

manual for the connected devices for further infor-

mation.