beautypg.com

Gas supply – Raypak 500 User Manual

Page 16

background image

Gas Supply

Gas piping must have a sediment trap ahead of the

heater gas controls, and a manual shut-off valve lo-

cated outside the heater jacket. It is recommended

that a union be installed in the gas supply piping adja-

cent to the heater for servicing. The gas supply

pressure to the heater must not exceed 10.5 in. WC for

natural gas or 13.0 in. WC for propane gas. A pounds-

to-inches regulator must be installed to reduce the gas

supply pressure if it is higher than noted above. This

regulator should be placed a minimum distance of 10

times the pipe diameter upstream of the heater gas

controls. Refer to Table J for maximum pipe lengths.

Gas Supply Connection

The heater must be isolated from the gas supply pip-

ing system by closing the upstream manual shut-off

valve during any pressure testing of the gas supply

piping system at test pressures equal to or less than

1/2 psi (3.45 kPa). Relieve test pressure in the gas

supply line prior to re-connecting the heater and its

manual shut-off valve to the gas supply line. FAILURE

TO FOLLOW THIS PROCEDURE MAY DAMAGE

THE GAS VALVE. Over-pressurized gas valves are

not covered by warranty. The heater and its gas con-

nections shall be leak-tested before placing the

appliance in operation. Use soapy water for leak test.

DO NOT use an open flame.

DANGER: Make sure the gas on which the heater

will operate is the same type as specified on the rat-

ing plate.

CAUTION: The heater must be disconnected from

the gas supply during any pressure testing of the gas

supply system at test pressures in excess of 1/2 psi

(3.45 kPa).

Gas Supply Pressure

A minimum of 4.0 in. WC and a maximum of 10.5 in.

WC upstream gas pressure is required under load and

no-load conditions for natural gas. A minimum of 4.0

in. WC and a maximum of 13.0 in. WC is required for

propane gas. The gas pressure regulator(s) supplied

on the heater is for low-pressure service. If upstream

pressure exceeds these values, an intermediate gas

pressure regulator, of the lockup type, must be

installed.

When connecting additional gas utilization equipment

to the gas piping system, the existing piping must be

checked to determine if it has adequate capacity for

the combined load. The gas valve pressure regulator

on the heater is nominally preset as noted in Table I.

During normal operation, carbon dioxide should be 8.5

to 9.0% at full fire for natural gas and between 9.0 and

9.5% for propane gas. Carbon monoxide should be

‹150 ppm.

Fig. 10: Gas Supply Connection

CAUTION: Do not use Teflon tape on gas line pipe

thread. A pipe compound rated for use with natural

and propane gases is recommended. Apply

sparingly only on male pipe ends, leaving the two

end threads bare.

CAUTION: Support gas supply piping with

hangers, not by the heater or its accessories. Make

sure the gas piping is protected from physical

damage and freezing, where required.

NOTE: Manifold pressures should be ±0.3 in. WC.

Table I: Manifold Gas Pressure Settings

16

Model

No.

Manifold Pressure (in. WC)

Natural Gas

Propane Gas

High

Low

High

Low

300

-0.2

-0.1

-0.2

-0.1

500

-0.3

-0.1

-0.3

-0.1

850

-3.2

-0.2

-2.7

-0.1

This manual is related to the following products: