34

5. If the appliance fails to start, refer to the

Troubleshooting section in the back of this manu-

al.

User Menu

The user menu consists of several items that can be

adjusted. To access the user menu, press and hold the

ENTER/MENU key for 5 seconds. Using the UP and

DOWN, and LEFT and RIGHT arrow keys, enter 600,

then press ENTER/MENU. Scroll through the list of

adjustable items by pressing the LEFT or RIGHT

arrow keys. Once the desired item is displayed, press

the ENTER/MENU key to select it. The screen will

begin to flash. Press the DOWN arrow key to decrease

the values, and the UP arrow key to increase them. To

store the changes, press the ENTER/MENU key. The

display returns to normal mode after one minute.

Pressing the ESC/RESET key before storing changes

will restore the original value. Refer to Fig. 32 for dis-

play and key locations.

Adjusting the XFyre Setpoint

To adjust the temperature on the XFyre:

– Press the ENTER/MENU key for 5 seconds to

bring up the code menu. Enter 600 to access the

user menu.

– Press the DOWN arrow key to decrease the tem-

perature (minimum setpoint is 50°F).

Operating Instructions

Remove the front door. If you smell gas, STOP. Follow

listed safety instructions. If you do not smell gas, fol-

low the next steps.

1. Turn on all electric power to appliance.

2. Adjust the temperature setpoint of the XFyre as

desired. The factory default setting is 160°. If

changes are necessary follow “Adjusting The

XFyre Setpoint” in this section.

3. On the initial start-up of units with gas pressure

switches, the control user interface will display

flue/gas press. This is a low gas pressure switch

lock-out from the factory-installed low gas pres-

sure switch. You will also see a yellow LED

illuminated under the cover of the low gas pres-

sure switch. Once the gas is turned on, reset the

gas pressure switch by FIRMLY pressing on top of

the plastic cover over the red reset button. The

yellow LED will go out after the switch has been

reset. Press and hold the ESC/RESET key on the

control panel for about 4 seconds to begin normal

operation.

4. Set the thermostat to the desired setting.

NOTE: Before you can change the temperature

from the factory setting of 160 degrees, you must

make sure none of the thermostats are calling for

heat. The controller will not memorize a program

setting while in a heating cycle.

Fig. 31: Condensate Drain Sensor

Blocked Condensate Drain Sensor

This boiler is equipped with a condensate sensor to

prevent operation when the condensate water level is

too high. The boiler shutting down from the conden-

sate sensor is indicative of a blocked drain or problem

with the condensate management system. The con-