Nortel Networks 5000i User Manual
Page 24

then another code-approved method must be used. (The isolated ground conductor is noted 
in the National Electrical Code{ XE "National Electrical Code" }{ XE "NEC" \t "See National 
Electrical Code" }, Section 250-74, Exception 4.) Use of an isolated ground rod or grounding to 
a water pipe is not acceptable. 
An isolated/insulated ground conductor, equal to or larger in size than the heaviest gauge 
AC feeder conductor in the circuit, should be bonded to the ground bus in the building main 
power panel. Route it with the circuit conductors in the wiring conduit. Pass this ground 
through any intermediate panel boards without connection to the panel board grounding 
terminal bars. The National Electric Code, cited above, allows for the installation at the 
intermediate panel board of an isolated ground bus, constructed from a terminal block kit, 
for the interconnection of the isolated ground conductor. 
This isolated/insulated ground conductor runs as a single, uninterrupted circuit between the 
building main power panel and the 5000i system branch power panel. It forms the 
interconnection point for the third-wire { XE "Ground:Third-wire" \i }grounds of all 5000i 
system components. Connect all 5000i system component third-wire grounds to this ground; 
do not connect any equipment other than 5000i system components to this ground conductor. 
This condition is met if all system components are plugged into the { XE "Switched 
convenience outlet" \t "See Convenience outlet" }switched convenience outlet{ XE 
"Convenience outlet:switched" }{ XE "Electrical outlet, convenience" \t "See convenience 
outlet" \i }{ XE "Outlet, convenience" \t "See Convenience outlet" } in the base of the scanner. 
1) At some sites, local regulations require that all installed equipment be connected
to a system common ground. In this case, connect all 5000i system components to 
the common ground at only one point. Connect third wire grounds of system 
components onto a common bus that is connected to the common ground at a 
single point. 
 
2) Make sure the equipment third-wire { XE "Ground:Third-wire" \i }ground (green
wire) does not become connected to the conduit at the outlet box or connector. To 
avoid an inadvertent connection, use a NEMA 5-20R type isolated-ground 
receptacle, such as a 
Hubble IG-5362. 
Grounding in Multi-Story Buildings{ XE "Grounding:In multistory 
building" \i } 
When installing the 5000i system in a multi-story building{ XE "Multistory building, 
grounding" \t "See Grounding in multistory building" }, provide a low noise ground by 
connecting the isolated { XE "Conductor:Isolated/insulated" }ground { XE 
"Ground:Conductor" \i }of the system to the structural steel of the building. Install the 
isolated ground system as described above. In addition, bond one end of a heavy gauge wire 
or copper braid to the isolated ground bus in the branch circuit panel serving the 5000i 
system. Weld the other end of this wire or braid to the nearest vertical steel structural 
member. Do not substitute a water pipe or an isolated ground rod for the vertical steel 
member. 
Page 12
5000i Scanner Installation Guide
