3 table of mewtocol−com error code – Panasonic FP2 User Manual
Page 47

Specifications
FP2−CCU
6 − 5
6.3
Table of MEWTOCOL−COM Error Code
6.3
Table of MEWTOCOL−COM Error Code
21 Data Error:
•
Situation
A data error occurred during communication.
There are three types of data errors: parity errors, framing errors, and unit
receive buffer errors.
•
Example of error
This occurs if the communication format between the host computer side
and the PLC side is different.
•
Precautions when the FP2 Computer Communication Unit is being
used
If the parity settings are different, the ERR LED lights but no error code is
returned.
•
ERR LED on the FP2 Computer Communication Unit
Lights
22 Overrun Error:
•
Situation
The CPU unit buffer is full, and no more data can be received.
•
Example of error
This occurs if a command being sent before a response has been
returned in cases such as commands being sent continuously from the
host side.
•
ERR LED on the FP2 Computer Communication Unit
Lights
24 Transmission Format Error:
•
Situation
There is an error in the setting of a hierarchy control command.
•
Example of error
This occurs if a hierarchy control command has not been notated
correctly.
•
ERR LED on the FP2 Computer Communication Unit
Lights