Troubleshooting requiring eaton service – Powerware 9135 Two-in-One UPS 5000/6000 VA User Manual
Page 75
TROUBLESHOOTING
EATON Powerware
®
9135 Two−in−One UPS (5000/6000 VA) User’s Guide
S 164201726 Rev 1
www.powerware.com
69
Troubleshooting Requiring Eaton Service
NOTE In case of multiple fault, press the
button and the
button to get access to
further details.
esc
Escape
Up
Down
Enter
Figure 43. Troubleshooting LED
Display
Signification
Correction
POWER MODULE FAULT
Internal power module fault detected. Use
"Enter" button to display details.
In Parallel: see the note below to start the
other UPS alone.
Call the Help Desk. Replace the power
module (see page 63).
BATT MODULE FAULT
Battery fault detected during the battery
test. Use "Enter" button to display details.
Call the Help Desk. Replace the battery tray
(see page 64).
FRAME FAULT
Internal chassis fault detected. Use "Enter"
button to display details.
Call the Help Desk.