Powerware 9135 Two-in-One UPS 5000/6000 VA User Manual
Page 59

OPERATION
EATON Powerware
®
9135 Two−in−One UPS (5000/6000 VA) User’s Guide
S 164201726 Rev 1
www.powerware.com
53
Table 4. Output Settings
Function
Factory Setting
Options
Comments
Output Voltage
EU Models: 230V
U Models: 208V
200V / 208V / 220V /
240V / 250V
Freq Converter
Disable
Enable
Output Frequency
EU Models: 50 Hz
U Models: 60 Hz
60 Hz
User selectable under
frequency−converter mode
Eco Mode
Disable
Enable
Slew Rate
1 Hz / sec
0.5 Hz / sec
Bypass Transfer
If bypass Ac nok?
Yes
No
Transfer to bypass if utility power is
out of tolerance
Interrupt Time
10 ms
20 ms, ...... , 200 ms
Break time calibration during load
transfer on utility power out of
tolerance
Overload Prealarm
105%
40%, 50%, 70%
Alarm if threshold is overrun
Table 5. ON/OFF Settings
Function
Factory Setting
Options
Comments
Cold Start
Disable
Enable
Start on battery
Forced Reboot
Enable
Enables automatic restart of the
system even if utility power is
restored before the end of the
shutdown sequence
Auto Restart
Enable
Disable
UPS restarts automatically when
utility power is restored
Energy Saving
Disable
Enable
Automatic shutdown on battery if
output load level <10%
Sleep Mode
Enable
Disable
Remote Command
Enable
Disable
Enables consideration of shutdown or
restart orders from software to be
authorized