SPECIFICATIONS
EATON Powerware
®
9135 Two−in−One UPS (5000/6000 VA) User’s Guide
S 164201726 Rev 1
www.powerware.com
66
Table 12. Power Connections
Model
Input Connection
Output Receptacles
U Models
10 ft, L6−30P power cord
(4) NEMA L6−30R
EU Models
Hardwired
Hardwired with
(8) 10A, IEC 320−C13; (2) 16A, IEC 320−C19
Table 13. Environmental and Safety
U Models
EU Models
Operating Temperature
0°C to 40°C (32°F to 104°F)
Storage Temperature
−25°C to 40°C (−13°F to 104°F)
Relative Humidity
5–95% noncondensing
Operating Altitude
Up to 1,000 meters above sea level
Audible Noise
Less than 46 dBA Normal mode, typical load and Battery mode
Surge Suppression
ANSI C62.41 Category B, IEC 61000−4−5
Safety Conformance
UL 1778;
CSA C22.2, No. 107.1;
NOM−019−SCFI
UL 1778;
CSA C22.2, No. 107.1;
EN 62040−1−1, IEC 60950−1, IEC 50091−1−1
Agency Markings
cUL, NOM
TUV(GS), CE, cUL, C−tick
EMC (Class A)
FCC Part 15
EN 62040−2 C1, AS 62040−2 C1, FCC Part 15
Table 14. Battery
UPS Configuration
(15) 12V, 5.5 Ah internal batteries
EBM Configuration
(2 strings of 15) 12V, 5.5 Ah internal batteries
Type
Sealed, maintenance-free, lead-acid
Table 15. Battery Runtimes
UPS
UPS Internal Batteries
+1 EBM
+2 EBMs
+3 EBMs
+4 EBMs
5000 VA
5 min
22 min
41 min
1 hr 2 min
1 hr 23 min
6000 VA
4 min
17 min
33 min
50 min
1 hr 7 min
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.