beautypg.com

Powerware 685 User Manual

Page 53

background image

A---11

Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets

Installation Manual

164201408 Rev. P00 053002

DESCRIPTION:

DRAWING NO:

1 of 1

Series 685 / 1085 Configurations

SHEET:

164201408--4

BATTERY

CABINET

BATTERY

CABINET

UPS

CABINET

(E4)

BATTERY

CABINET

BATTERY

CABINET

UPS

CABINET

BATTERY

DISCONNECT

Powerware 9350 30 through 160

Battery Cabinets integral to UPS

and connected using Manufacturer supplied wiring

Battery Cabinets located separately

4 Cabinets Maximum

4 Cabinets Maximum

Contractor Wiring (2): See

Table C of Appendix A to size

Contractor Supplied wiring

CONTRACTOR

WIRING (2)

CONTRACTOR

WIRING (1)

Contractor Wiring (1): Refer to UPS manual to size wiring

(E5)

(E4)
(E5)

Powerware 9350 30 through 160

from the UPS

NOTE: The term “Separate” refers to battery cabinets that are not physically attached

to the UPS, are wired with external contractor supplied wiring, and use a single

overcurent protection and disconnect device located near the batteries.

The term “Integral” refers to battery cabinets that are physically attached to the

UPS and the wiring between them is internal. The power wiring is supplied

with the system, and they use the UPS battery switch as the battery isolation

device.

The wire size rating for products up to and including the 160/160 are for the

total battery supply. Since these UPS units can only land one wire per DC

connection point, a common DC collector including an isolation device and

overcurrent protection should be used. Refer to applicable national or local

code requirements for your installation.

This manual is related to the following products: