12

Powerware 9350 Series 685 and 1085 Auxiliary Battery Cabinets

Installation Manual

164201408 Rev. P00 053002

1.

Make sure that the UPS is properly installed and secured with its leveling feet.

2.

Roll the battery cabinet to a spot near the right-hand side of the UPS, as

shown in Figure 7.

3.

The field kit is attached with cable ties to the frame inside the door. Remove

and retain the field kit for later use.

4.

If necessary, remove the cosmetic covers and hanger brackets from the

right-hand side of the UPS. Save covers, screws, and brackets for later reuse.

5.

Push the battery cabinet toward the UPS cabinet until the doors are flush with

each other.

6.

Three cabinet attachment brackets are provided for securing each cabinet at

the top and bottom. Two flat brackets join the tops of the cabinets, one at the

front and one at the back. A larger flat bracket joins the cabinets at the

bottom. Attach the flat brackets to the cabinet tops first.

7.

For Series 685 Battery Cabinets, remove the right-hand screw from the top

right door hinge of the UPS cabinet. Align the hole in one flat bracket over this

screw hole, and the other hole over the hole in the top of the battery cabinet.

Replace the screw in the hinge, and attach the other end of the bracket to the

top of the battery cabinet using an M4×10 hex screw from the field kit (see

Figure 7).

8.

For Series 1085 Battery Cabinets, remove the right-hand screw from the top

right door hinge of the UPS cabinet, and the right-hand screw from the top left

door hinge of the battery cabinet. Align the holes in the flat bracket over these

screw holes and then replace the screws in the hinges (see Figure 7).

9.

Align the holes in the other small flat bracket with the two holes in the top rear

of the UPS and the battery cabinet. Attach each end to its mating hole using

an M4×10 hex screw from the field kit (see Figure 7).

NOTE: Perform Steps 10 through 13 for the Series 1085 Battery Cabinet.

Perform Steps 14 through 18 for the Series 685 Battery Cabinet.

10.

Locate the large flat bracket from the field kit. Place one end of the bracket

over the stud on the bottom side of the UPS cabinet lower right-hand hinge,

and the other end over the stud on the bottom side of the lower right-hand

hinge on the Series 1085 Battery Cabinet (see Figure 8).

11.

Attach the bracket to the hinges with two M8 self-locking nuts from the field kit.