Troubleshooting
64
Powerware
®
FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide
:
Rev A www.powerware.com
Table 15. Inverter Codes
Inverter Code
Meaning
Explanation
T
System Test
UPS went to inverter to test the batteries.
B
Brownout
AC input voltage was too low.
L
Line Loss
AC input power was lost.
M
Manual
The inverter was started manually.
F
Frequency
Input frequency was too high or too low.
R
Reset
A system reset was performed.
Reading the Alarm Log from a Terminal or Computer
To display the Alarm Log on a terminal or computer, you can use the
alarmlog or logs command (see “Entering Commands from a Terminal
or Computer” page 44). These commands display up to 20 log entries in
a table. For example, the log might look like this table:
Active
EventDate
EventTime
Duration
Code/Event
No
08/25/1993
11:25:32
00:00:45
J-User Test Alarm
No
08/24/1993
12:13:18
00:01:08
A-Low Battery
No
08/24/1993
12:05:07
00:08:11
B-Near Low Battery
The table shows whether the alarm is active now (Active), the date and
time of each alarm, how long it lasted (Duration), and what caused the
alarm (Code/Event).
You can also display parameter 25 to view the Alarm Log; this display is
the same as the control panel display.