Troubleshooting

61

Powerware

®

FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide

:

Rev A www.powerware.com

What To Do

What It Means

Alarm

Message

Audio

Code

Letter

J

:

– – –

User Test

Alarm

The user is testing the alarm feature.

To start the user test alarm from the
control panel, press [CTRL]-[8] [ENTER]
[ENTER]. Repeat the procedure to turn the
alarm off.

K

:

Hi

Transfmr

Temp

The transformer temperature is too high. If
the temperature reaches a preset point, the
UPS shuts down.

The UPS may have shut down; if so,
contact your service representative. If the
UPS has not shut down, shut down your
equipment or bypass the UPS; then, turn
the UPS off and contact your service
representative.

L

:

: :

Check

Charger

The UPS has detected a charger problem.

Contact your service representative.

M

– –

Check

Battery

The batteries have failed the automatic
system test.

Contact your service representative.

N

:

Check

Inverter

The inverter has failed the automatic
system test.

Contact your service representative.

O

– – –

Memory

Check

Possible microprocessor problem.

Shut down your equipment or bypass the
UPS; turn off the UPS. Contact your service
representative.

P

:

– –

:

Emergency

PwrOff

The Remote Shutdown feature has been
activated at the RS-232 port (see “Remote
Shutdown” on page 47.)

To restart the UPS, disconnect the signal to
Pin 21 on the RS-232 port. If you have a
control panel, put the UPS in Auto mode. If
not, turn the On/Off switch off and then on
again.

Q

– –

:

Hi PFM

Res

Temp

The Power Factor Module’s temperature is
too high. If the temperature reaches a
preset point, the UPS shuts down.

If the UPS has shut down, contact your
service representative. If not, shut down
your equipment or bypass the UPS; then,
turn the UPS off and contact your service
representative.

R

:

:

Probe

Missing

A temperature probe is missing or
damaged.

The UPS may shut down. Contact your
service representative.

S

: : :

High AC

Input

The input voltage is higher than the alarm
setting.

Contact your service representative.