Specifications

55

Powerware

®

FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide

:

Rev A www.powerware.com

18 kVA/

15 kW

12.5 kVA/

10 kW

10 kVA/

7.5 kW

7 kVA/

5 kW

5.3 kVA/

3.7 kW

4.3 kVA/

3 kW

Model

Output Voltage and Maximum Output Current

3

FE:

120 Vac
208 Vac
220 Vac
240 Vac

QFE: 2

20 Vac

230 Vac
240 Vac

34A
20A
19A
17A
19A
18A
17A

44A
26A
24A
22A
23A
22A
21A

58A
34A
31A
29A
31A
30A
28A

82A
48A
46A
41A
45A
43A
41A

103A

58A
55A
51A
56A
52A
51A

149A

84A
82A
73A
84A
76A
73A

Efficiency On AC
Line

90%

90%

90%

90%

91%

92%

On Line BTU/hour:
kW/hour:

1138

.333

1403

.411

1896

.556

2844

.833

3375

.989

4452

1.3

Audible Noise (dB)

50

51

54

55

56

57

Runtime (minutes)
Full Load:
Half Load:

8

20

20
50

12
33

11
26

18
48

10
26

Weight :

Without Battery:

60 Hz Models:
50 Hz Models:

With Battery:

60 Hz Models:
50 Hz Models:

N Cabinet with
Standard Batteries

243 lb

115.7 kg

348 lb

163.3 kg

268 lb

131.1 kg

484 lb

229.1 kg

362 lb

176.5 kg

578 lb

274.4 kg

442 lb

217.7 kg


395 lb

(179.2 kg)

505 lb

251.3 kg


535 lb

(242.7 kg)

625 lb

312.1 kg


675 lb

(306.2 kg)

Dimensions
(H x W x D)

5

29.5” x 15.5” x 25”

75.0 x 39.5 x 63.5 cm

36.5” x 19” x 32”

93.0 x 48.5 x 81.5 cm

1

FE 4.3 kVA,5.3 kVA, and 7 kVA models have optional 120 Vac input voltage.

2

Size input protection according to all applicable local or national codes. Fuse and circuit breaker sizes vary. Sizes shown

are for the U.S. and Canada.

3

At 0.7 to 0.83 leading power factor.

4

FE and QFE 10 kVA, 12.5 kVA, and 18 kVA models do not have internal batteries. Batteries are in a separate battery

cabinet or rack.

5

If your model has an internal bypass switch, add 8” (20.0 cm) to the depth.