Startup for the FE and QFE 4.3–18 kVA UPS

To start the FE and QFE 4.3–18 kVA UPS, use the following steps:

1. Confirm the equipment to be protected by the UPS is powered

off.

2.

For Plug-Receptacle UPSs:

Verify that the AC input power is off

at the service panel. Plug the UPS power cord into a power
outlet.

NOTE If the plug does not match your receptacle outlet, ask your electrician to install
the proper outlet.

For Hardwired UPSs:

Confirm that an electrician has completed

and tested the connection to the proper power source and
connected your protected equipment according to the
Powerware FERRUPS FE/QFE UPS (500 VA–18 kVA) Installation
Guide
. Confirm that your AC line disconnect switch and the
UPS ON/OFF switch are both in the OFF position.

3. If your UPS has a DC switch, turn on the switch according to

the UPS model:

4.3–7 kVA:

If you have an external battery cabinet(s) with a DC

switch, turn the switch to the ON position.

If you do not have an external battery cabinet(s): unlock the
UPS front cover panel using the FERRUPS key and remove the
front cover panel. Locate the DC switch behind the UPS front
cover panel. If there is a precharge button next to the switch,
press it for a few seconds. Turn the DC switch to the ON
position and reinstall the UPS front cover panel.

10–18 kVA:

If you have an external battery cabinet(s) with a DC

switch, turn the switch to the ON position.

4.

Starting the UPS on battery power:

Use the key to turn the

ON/OFF switch to the ON position. After a brief self-check, the
BATTERY POWER and READY indicators illuminate. The UPS
beeps every 20 seconds, indicating the UPS is running on
battery power. The control panel scrolls this display:

)(55836

0RGH

$XWR

&KDUJHU

2II

%HHSHU (QDEOHG