Operation

34

Powerware

®

FERRUPS FE/QFE UPS (500 VA–18 kVA) User’s Guide

:

Rev A www.powerware.com

Explanation

Parameter Name

(Short Form)

Password

Sample Display

Parameter

Number

14

14 XfmrTemp 28c

Change Not

Allowed

xfmrtemp

(xt)

The temperature of the transformer. The UPS
sounds an alarm and shuts down if this value
is too high.

NOTE

This parameter is only active on some

models; for other models, the display always
shows -63c.

15

15 Unit ID

Network #1 UPS

None

(See “Entering

Passwords” on

page 28.)

unitident

(id)

UPS ID. An identification string that can be
configured for use with your network.

16

16 FullLoad% 075

Change Not

Allowed

fullload

(l)

Percent of Full Load. The percentage of the
UPS’s total capacity that is actually being
used by your equipment.

17

17 Watts 374

Change Not

Allowed

watts

(w)

The total “real power” your equipment is
drawing from the UPS.

18

18 PF 0.73 Dist

Change Not

Allowed

powerfact

(pf)

The power factor of your equipment; the
difference in the way it draws voltage and
current. Power factor is equal to Watts Out
(parameter 17) divided by VA Out
(parameter 5). This parameter also tells
whether the power factor is leading (Lead),
lagging (Lag), or distortion (Dist).

19

19 VALimit 500

Change Not

Allowed

valimit

(val)

The maximum volt-amps the UPS can supply
to your equipment at the present power
factor. The UPS sounds an alarm when VA
Out (parameter 5) is higher than this value.

20

20 #PwrOut 1

Change Not

Allowed

powerout

(po)

The number of times there has been a loss of
input power since you started the UPS.

21

21 #OvrLds 0

Change Not

Allowed

overloads

(ol)

The number of times the UPS has sensed an
overload; that is, the number of times VA Out
has been greater than VA Limit.

22

22 SysHrs 00000

Change Not

Allowed

syshours

(sh)

The total number of hours the UPS has been
operating, regardless of mode. This number
does not increase when the UPS ON/OFF
switch is in the OFF position.

23

23 InvMin 0000.0

Change Not

Allowed

invmin

(im)

The total number of minutes the inverter has
run since startup.