Description

The addressable Monitor Module IM-10 provides 10

independent inputs and serves for the line-monitored

integration of contact detectors, such as manual call

points, sprinkler system contacts or supervising con-

tacts, into the bidirectional communication on the ADM

loop with System Sensor/200 protocol.

The Monitor Module IM-10 occupies 10 consecutive

addresses on the ADM loop. During commissioning, the

base address, i.e., the lowest one of the 10 addresses,

is set by means of decadic rotary switches.

The optional steel sheet Surface Mounting Box

M200SMB-MM accommodates one Monitor Module

IM-10 or Control Module CR-6.

• ADM loop technology with

System Sensor/200 protocol

• 10 independent inputs with

monitoring for wire breakage and

short circuit

• Status LED for each input
• Setting of module address via

decadic rotary switches

• Mounting in surface mounting box

Specifi cations

Operating voltage

Supply through loop voltage

Current consumption

approx. 3.5mA (quiescent)

Ambient temperature

0°C to +50°C

Dimensions L × W × H

172 Ч 147 Ч 25 (mm)

Weight

500g

Order number

249115

Order name

Monitor Module 10xSurv.In/Anal./200/SS IM-10

Surface Mounting Box

Ambient temperature

0°C to +50°C

Dimensions L × W × H

285 Ч 225 Ч 62 (mm)

Colour

cream

Weight

2kg

Order number

249117

Order name