beautypg.com

Liebert UPS System User Manual

Page 91

background image

Chapter 7 Troubleshooting

85

No.1

Fault description

Reason

Actions to be taken

30 Rectifier

fan

fails

Rectifier fan is abnormal

Replace the fan in time and the UPS can
recover automatically

31

Rectifier contactor
abnormal

Rectifier contactor can’t be closed or
opened normally

Notify the service dept for repairing

32

Auxiliary contactor
abnormal

Auxiliary contactor abnormal can’t
be closed or opened normally

Notify the service dept for repairing

33

Auxiliary power supply
1 fails

At least one auxiliary power supply
fails

Notify the service dept for repairing

34

Rectifier over current

The IGBT of rectifier has over
current resulting in the shut down of
rectifier.

Notify the service dept for repairing

35 Inverter

asynchronous

Inverter is asynchronous with
bypass

Check if the bypass is normal. The fault
alarm stops automatically after the
bypass recovers normal

36

Inverter fails

Inverter output fails and shuts down Notify the service dept for repairing

137

Inverter heatsink over
temperature

Inverter heatsink temperature is too
high

The UPS can recover automatically.
Check the environment and ventilation

38

Inverter fan fails

Inverter fan is abnormal

Replace the fan in time and the UPS can
recover automatically

39 Inverter

SCR

fails

Inverter SCR fails and has no
output. UPS shuts down

Notify the service dept for repairing

40

Auxiliary power supply
2 fails

At least one auxiliary power supply
fails

Notify the service dept for repairing

41 Inverter

over

current

The IGBT of inverter has over
current resulting in the shut down of
inverter.

Restart the inverter, if the fault can’t be
cleared, notify the service dept for
repairing.

42

Shutdown due to low
bus voltage

DC bus voltage is too low resulting
in the shutdown of inverter

Check whether there is fault in rectifier
side, if no, then check whether overload
occurs. Restart after clearing the fault.

43

Output transformer
over temperature

Output transformer temperature is
too high

Auto recovery, ambient and ventilation of
UPS should be checked.

44 overload

Load is too heavy

Disconnect unnecessary load and ensure
the safety.

45

Overload exceeds
normal time

Over load occurs in inverter mode,
transfers to bypass mode

If the load decreases after 5 minutes, the
system will back to inverter mode

46

Output fuse blows up Output fuse blows

Notify the service dept for repairing

47

AC output over
voltage

Output over voltage

Notify the service dept for repairing

48 Output

surge

current

Surge current occurs in bypass
mode, the system shutdown

Avoid applying big load abruptly and short
circuit