4 lcd indication for fault information – Liebert UPS System User Manual
Page 89
Chapter 7 Troubleshooting
83
7.4 LCD indication for fault information
The LCD on the UPS displays the fault information of Table 7-1 and Table 7-2. The
user should locate and analyze the fault according to the tables and feedback the
fault information to our service engineers.
Table 7-1 Fault information
No.1
Fault description
Reason
Actions to be taken
1
Communication of
inverter fails
Communication between monitoring
unit and inverter fails
Notify the service engineer for repairing
2
Communication of
rectifier fails
Communication between monitoring
unit and rectifier fails
Notify the service engineer for repairing
3
Ambient over-
temperature
over-temperature of UPS room
Check the ventilation of UPS room
4
Environment
parameter 1 abnormal
Environment parameter channel 1
has alarm
Check the devices relating to the channel
5
Environment
parameter 2 abnormal
Environment parameter channel 2
has alarm
Check the devices relating to the channel
6
Environment
parameter 3 abnormal
Environment parameter channel 3
has alarm
Check the devices relating to the channel
7
Environment
parameter abnormal
12V environment parameter channel
has alarm
Check the devices relating to the channel
8
Rectifier input voltage
abnormal
Line-to-neutral voltage of rectifier
exceeds normal operation range
Check the line-to-neutral voltage
amplitude of rectifier
9
Rectifier input under-
voltage
Line-to-neutral voltage of rectifier
lower than 305V, but higher than
208V
Check the line-to-neutral voltage
amplitude of rectifier
10
Rectifier’s input
voltage frequency is
abnormal
Rectifier frequency exceeds the
normal range
Check the rectifier’s input voltage
frequency
11
Input fuse blows
Rectifier input fuse blows up
Notify the service dept for repairing
12
Input transformer over
temperature
Temperature of input transformer is
too high
Check the ambient temperature and
ventilation
13
Input phase rotation
reverse
Rectifier’s input phase rotation is
reverse
Notify the UPS service engineer, check
the wiring of rectifier input cables
14
Input softstart fails
Input softstart fails
Notify the service dept for repairing