Chapter 9 Optional Parts
101
Chapter 9 Optional Parts
9.1 Battery
9.1.1 Capacity selection
Calculate the discharging current according to rated load capacity and then select
the battery according to the current and the battery backup time required by user.
There are various specifications of battery, we recommend that 30 12V battery cells
should be connected in series to form a battery string. The capacity of battery cell
can be 38Ah, 65Ah and 100Ah.
Note
If the battery capacity exceeds 100Ah
,the user should connect the battery of
same model and same capacity in parallel or use large capacity 2V battery to make
up the battery group.
The capacity data of battery string are listed in Table 9-2 and the capacity data are
selected according to rated load. Select the battery of 70%~100% rated capacity
according to the actual load and required backup time.
Table 9-1 Battery capacity equipped for single UPS (Ah,25℃)
UPS
capacity
20kVA 30kVA
40kVA
60kVA
Discharging
current
50A 75A
100A
150A
Backup time
Battery capacity(Ah)
15min
38 65
100
100
30min
65 65
100
150
1h
100 130
180
340
2h
150 200
340
420
3h
200 340
420
630
4h
250 340
510
680
5h
340 420
630
840
6h
340 510
680
1020
8h
420 630
840
1260