Description

Specifi cations

The Thermal Max Detector GM-55000-137 recognises

a maximum temperature of 90°C as sign of fi re. It com-

plies with Class CS and can be used up to a room height

of 6m.

Addressable conventional technology is used for alarm

transmission to the fi re detection control panel. By

means of the optional Address Module NG60-1, each

detector can be addressed individually. With that, the

activated detector can also be safely identifi ed directly

on the control panel.

The detector can be attached to various bases and it

can be protected against theft.

Operating voltage

Supply through the detector line voltage

Current consumption

typ. 45µA (quiescent)

Alarm temperature

typ. 90°C

Operating temperature

max. +80°C (continuous operation)

Ambient temperature

-20°C to +90°C (no condensation or icing)

Relative humidity

0 – 95% (no condensation)

Dimensions ш Ч H

100 × 42 (mm)

Colour

white

Weight

80g

Approval

VdS G200062

Order number

242027