LST 55000-847 User Manual
Description

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
55000-847_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The addressable Module 55000-847 serves for the
line-monitored integration of contact detectors, such
as manual call points, sprinkler system contacts or
supervising contacts, into the bidirectional communica-
tion on the ADM loop with Apollo/Discovery protocol.
Furthermore, it can be used to actuate external devices
by means of a relay output with two dry change-over
contacts, via the ADM loop. In addition to the monitored
input and the relay output, the module has an opto-cou-
pled input for monitoring an external voltage.
The address is easily selected by means of a built-in DIL
switch. Status LEDs indicate the condition of input and
output. The module has an integrated dual-isolator and
is fi tted into a plastic case.
• ADM loop technology with
Apollo/Discovery protocol
• One line-monitored input and one
relay output with two dry contacts
• Setting of module address by means
of address switch
• Integrated dual-isolator
• Status LEDs for input and output
Specifi cations
Operating voltage
Supply through loop voltage
Current consumption
approx. 1.5mA (quiescent)
Contact rating
1A/30VDC or AC
Ambient temperature
-20°C to +70°C
Dimensions L × W × H
150 Ч 90 Ч 48 (mm)
Colour
white
Weight
240g
Approval
VdS G201032
Order number
249076
Order name
Module 1xSurv.In 1xRel.Out/Apo 55000-847