General, Venting – Lochinvar Sync Condensing Boiler 1 User Manual
Page 21

21
Installation & Operation Manual
2
General
venting
(continued)
Figure 2-8 Near Boiler Stainless Steel Venting
The installer must use a specific vent starter 
adapter at the flue collar connection, 
supplied by the vent manufacturer to 
adapt to its vent system. See Table 2F for 
approved vent adapters. Discard CPVC 
starter piece.
NOTICE
Stainless steel vent
This product has been approved for use with stainless steel 
using only FasNSeal vent systems.
Use only the materials, vent systems, and 
terminations listed in Table 2F. DO NOT 
mix vent systems of different types or 
manufacturers. Failure to comply could 
result in severe personal injury, death, or 
substantial property damage.
ƽ WARNING
Installations must comply with applicable 
national, state, and local codes. Stainless 
steel vent systems must be listed as a 
UL-1738 approved system for the United 
States and a ULC-S636 approved system 
for Canada. 
NOTICE
Installation of a stainless steel vent system 
should adhere to the stainless steel vent 
manufacturer’s installation instructions 
supplied with the vent system.
NOTICE
STAINLESS STEEL VENT TERMINATION KITS
Kit Part Number
Model
Component Description
KIT30028
SB 1000 - 1500
6" PVC x 6" Stainless Steel Adapter
6" Stainless Steel Vent Termination
6" Stainless Steel Air Inlet
KIT30029
SB 1300 - 1500
6" PVC x 6" Stainless Steel Adapter
6" Stainless Steel x 7" Stainless Steel Adapters (2)
7" Stainless Steel Vent Termination
7" Stainless Steel Air Inlet
Table 2F Approved Stainless Steel Terminations and Adapters
REMOVE PVC/CPVC VENT
CONNECTOR WHEN
INSTALLING STAINLESS STEEL
The SYNC uses model specific combustion air intake and vent 
piping sizes as detailed in Tables 2A and 2B.
Increasing or decreasing combustion air 
or vent piping to sizes not specified in this 
manual is not authorized.
NOTICE
PVC/CPVC or ABS is acceptable air inlet pipe material.
NOTICE
