beautypg.com

Maintenance, Inspect ignition and flame sense electrodes, Check ignition ground wiring – Lochinvar Shield SNA285-125 User Manual

Page 56: Check all water heater wiring, Check control settings, Perform start-up and checks, Check burner flame, Check flame signal, Review with owner

background image

56

12

Maintenance

Inspect ignition and flame sense
electrodes

1. Remove the ignition and flame sense electrodes from

the water heater heat exchanger access cover.

2. Remove any deposits accumulated on the

ignition/flame sense electrode using sandpaper. If the
electrodes cannot be cleaned satisfactorily, replace with
new ones.

3. Replace ignition/flame sense electrode, making sure

gasket is in good condition and correctly positioned.

Check ignition ground wiring

1. Inspect water heater ground wire from the heat

exchanger access cover to ground terminal strip.

2. Verify all wiring is in good condition and securely

attached.

3. Check ground continuity of wiring using continuity

meter.

4. Replace ground wires if ground continuity is not

satisfactory.

Check all water heater wiring

1. Inspect all water heater wiring, making sure wires are in

good condition and securely attached.

Check control settings

1. Set the control module display to Parameter Mode and

check all settings. Adjust settings if necessary. See
Section 1 of this manual for adjustment procedures.

2. Check settings of external limit controls (if any) and

adjust if necessary.

Perform start-up and checks

1.

Start water heater and perform checks and tests
specified in Section 10 - Start-up.

2.

Verify cold fill pressure is correct and that operating
pressure does not go too high.

Check burner flame

1.

Inspect flame through observation window.

2.

If the flame is unsatisfactory at either high fire or low fire,
turn off water heater and allow water heater to cool down.
Remove the burner and clean it thoroughly using a
vacuum cleaner or compressed air. Do not use
compressed air to clean burner if performed inside a
building.

3.

Remove the burner, reference FIG. 12-2 below.

4.

When replacing the burner, ensure gasket is in good
condition and positioned correctly (FIG. 12-2).

Figure 12-2 Burner Assembly

Check flame signal

1. At high fire the flame signal shown on the display should

be at least 10 microamps.

2. A lower flame signal may indicate a fouled or damaged

flame sense electrode. If cleaning the flame sense
electrode does not improve, ground wiring is in good
condition, and ground continuity is satisfactory, replace
the flame sense electrode.

3. See Section 3 - Troubleshooting for other procedures to

deal with low flame signal.

Review with owner

1. Emphasize the need to perform the maintenance schedule

specified in this manual.

2. Remind the owner of the need to call a licensed

contractor should the water heater or system exhibit any
unusual behavior.

Installation & Service Manual

TM