Sidewall direct venting

(continued)

Vent/air termination – sidewall

All vent pipes and air inlets must terminate
at the same height to avoid possibility of
severe personal injury, death, or substantial
property damage.

Multiple vent/air terminations

1. When terminating multiple Shield water heaters terminate

each vent/air connection as described in this manual
(FIG. 3-5A).

ƽ WARNING

2. Place wall penetrations to obtain minimum clearance of

12 inches between edge of air inlet and adjacent vent outlet,
as shown in FIG. 3-5A for U.S. installations. For Canadian
installations, provide clearances required by CSA B149.1
Installation Code.

3. The air inlet of a Shield water heater is part of a direct vent

connection. It is not classified as a forced air intake with
regard to spacing from adjacent water heater vents.

12" MIN. BETWEEN EDGE OF AIR

INLET AND ADJACENT VENT OUTLET

VENT / AIR

TERMINATION

VENT

AIR

Figure 3-5A Multiple Vent Terminations (must also
comply with

Figure 3-1A)

Figure 3-5B Alternate Multiple Vent Terminations w/Field
Supplied Fittings (must also comply with

Figure 3-1B)