Maintenance

Follow the service and maintenance procedures given throughout this manual and in component literature
shipped with the water heater. Failure to perform the service and maintenance could result in damage to the
water heater or system. Failure to follow the directions in this manual and component literature could result
in severe personal injury, death, or substantial property damage.

The water heater should be inspected annually only by a qualified service technician. In addition, the
maintenance and care of the water heater designated in Table 12A and explained on the following pages must
be performed to assure maximum water heater efficiency and reliability. Failure to service and maintain the
water heater and system could result in equipment failure.

Electrical shock hazard – Turn off power to the water heater before any service operation on the water heater
except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in
electrical shock, causing severe personal injury or death.

Address reported problems

1.

Inspect any problems reported by the owner and correct
before proceeding.

Inspect water heater area

1.

Verify that water heater area is free of any combustible
materials, gasoline and other flammable vapors and
liquids.

2.

Verify that air intake area is free of any of the
contaminants listed in Section 1 of this manual. If any of
these are present in the water heater intake air vicinity,
they must be removed. If they cannot be removed,
reinstall the air and vent lines per this manual.

Inspect water heater interior

1.

Remove the front access cover and inspect the interior of
the water heater.

Eliminate all system or water heater leaks.
Leaking water may cause severe property
damage.

1.

Inspect all water and gas piping and verify to be leak free.

2.

Look for signs of leaking lines and correct any problems
found.

3.

Check gas line using the procedure found in Section 7 - Gas
Connections.

Check all piping for leaks

The condensate trap must be filled with
water during all times of water heater
operation to avoid flue gas emission from the
condensate drain line. Failure to fill the trap
could result in severe personal injury or
death.

ƽ WARNING

ƽ WARNING

ƽ WARNING

ƽ WARNING

ƽ WARNING

Figure 12-1 Condensate Trap

Clean condensate trap

1.

Remove the clean out cap on the bottom of the trap. Let
the condensate and any debris drain out.

2.

Replace the clean out cap.

3.

Fill with fresh water until the water begins to pour out of
the drain.

4.

Resume operation.

2" PVC CAP WITH

BLOCKED DRAIN SWITCH

CONDENSATE DRAIN

RETAINING SCREW

CONDENSATE FROM

HEAT EXCHANGER

REMOVABLE CAP

TO CLEAN OUT TRAP

Installation & Service Manual