beautypg.com

Sidewall direct venting, Vent/air termination – sidewall, Model kit number vent size – Lochinvar Shield SNA285-125 User Manual

Page 18

background image

18

3

Sidewall direct venting

Vent/air termination – sidewall

Follow instructions below when
determining vent location to avoid
possibility of severe personal injury,
death, or substantial property damage.

A gas vent extending through an exterior
wall shall not terminate adjacent to a wall
or below building extensions such as
eaves, parapets, balconies, or decks.
Failure to comply could result in severe
personal injury, death, or substantial
property damage.

Installation must comply with local
requirements and with the National Fuel
Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.

ƽ WARNING

ƽ WARNING

NOTICE

ƽ WARNING Do not connect any other appliance to the

vent pipe or multiple water heaters to a
common vent pipe. Failure to comply
could result in severe personal injury,
death, or substantial property damage.

Determine location

Locate the vent/air terminations using the following
guidelines:

1. The total length of piping for vent or air must not exceed

the limits given in the General Venting Section on page 17
of this manual.

2.

You must consider the surroundings when terminating
the vent and air:
a.

Position the vent termination where vapors will
not damage nearby shrubs, plants or air
conditioning equipment or be objectionable.

b.

The flue products will form a noticeable plume as
they condense in cold air. Avoid areas where the
plume could obstruct window views.

c.

Prevailing winds could cause freezing of
condensate and water/ice buildup where flue
products impinge on building surfaces or plants.

d.

Avoid possibility of accidental contact of flue
products with people or pets.

e.

Do not locate the terminations where wind eddies
could affect performance or cause recirculation,
such as inside building corners, near adjacent
buildings or surfaces, window wells, stairwells,
alcoves, courtyards, or other recessed areas.

ƽ WARNING Sidewall vent and air inlet terminations

must terminate in the same pressure
zone.

f.

Do not terminate above any door or window.
Condensate can freeze, causing ice formations.

g.

Locate or guard vent to prevent condensate damage
to exterior finishes.

Figure 3-1A Sidewall Termination of Air and Vent

Model

Kit Number Vent Size

SNR150-100 -- SNR200-100

KIT30045

3 inch vent

SNA285-125 -- SNA500-125

KIT30046

4 inch vent

Table 3A Sidewall Vent Kits

Do not exceed the maximum lengths of the
outside vent piping shown in FIG. 3-1B.
Excessive length exposed to the outside could
cause freezing of condensate in the vent pipe,
resulting in potential water heater shutdown.

Figure 3-1B Alternate Sidewall Termination of Air and
Vent w/Field Supplied Fittings

ƽ WARNING

If using the alternate sidewall termination:

3. The air piping must terminate in a down-turned elbow as

shown in FIG. 3-1B. This arrangement avoids recirculation
of flue products into the combustion air stream.

4. The vent piping must terminate in an elbow pointed

outward or away from the air inlet, as shown in FIG. 3-1B.

Installation & Service Manual

TM

TO BOILER

INTAKE AIR

CONNECTION

FROM BOILER

VENT PIPE

CONNECTION

VENT / AIR

TERMINATION

GRADE OR

SNOW LINE

12"

MIN

12"

MIN

TO

OVER-

HANG

POSSIBLE ORIENTATIONS