beautypg.com

Lennox Hearth MODEL MONTAGE 32FS User Manual

Page 12

background image

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE

1

Figure 11

- Manufactured Home Chimney Height Requirements

Chimney Height Requirements - Site Built Residential Home

The vent termination height required is - USA, 1-foot minimum; Canada

3-feet minimum above the roof penetration point as illustrated below (Ref.

USA - National Standard, NFPA 211 and Canada National Standard CSA

B365-01. Check with your local building official for additional require-

ments for your area.

Figure 10

-

Site Built Residential Home Chimney Height Requirements

Termination Cap

Must Be Listed To

UL 641 or ULC S609

USA 1 Foot Minimum

*

CANADA 3 Feet Minimum

Less than

10 Feet (3 m)

10 Feet

(3 m)

3 Feet (914 mm)

Minimum

2 Feet (610 mm) Min.

3 Feet

(914 mm)

Min.

m = meter

mm = millimeter

Requires A Listed Termination Cap *

Top Of Flue Must Be

3’ Higher Than High-

est Point Of Roof

Penetration

Top Of Flue Must Be ’

Higher Than Any Part Of

Roof Within 10’ Horizontal

Chimney Height Requirements - Manufactured Homes

The chimney must extend 3’ (.92m) above the level of roof penetration

and a minimum of 2’ (.61m) higher than any roof surface within 10’

(3m) (see below). Check with your local building officials for additional

requirements for your area.

To pass inspection in nearly any jurisdiction, the chimney must meet both

safety and exhaust flow requirements. The (3’ by) 2’ by 10’ rule applies

to both masonry and factory-built chimneys

* Ref. USA - National Standard, NFPA 211-latest edition and Canada

National Standard CSA B365-01-latest edition. Vents installed with a

listed cap shall terminate in accordance with the terms of the cap’s
listings.

Termination When Connected to Masonry Chimney or Existing

Class A Chimney

A flexible corrugated chimney liner has much greater resistance to the

flow of flue gases than does a rigid liner. For this reason we recommend

that a larger, 4” liner be used on vertical runs exceeding 15 feet or that

rigid venting be used . See Figure 12.

If a flexible corrugated chimney liner is used, it must be fully extended

to eliminate any sagging and to improve the exhaust flow.

Figure 12

- Existing Chimney Terminat

ion

Listed Pellet Vent

Termination Cap

Chase Cover

1’ Section of PL Vent

(listed to UL 641 or

ULC S609)

3” or 4” liner

(listed to UL 1777

or ULC S635)

Termination When

Connected to Masonry

Chimney or Existing

Class A Chimney

Termination height is

measured above the

highest point where

it passes through the

roof surface.

*Min. ft. clearance

is required to com-

bustibles (i.e. cedar

shake roof, etc.)