Building Safety. Building Security.

Description

The addressable Control Module CR-6 serves for the ac-

tuation of external devices by means of 6 independent

dry relay contacts, via the bidirectional communication

on the ADM loop with System Sensor/200 protocol.

The Control Module CR-6 occupies 6 consecutive

addresses on the ADM loop. During commissioning, the

base address, i.e., the lowest one of the 6 addresses,

is set by means of decadic rotary switches.

The optional steel sheet Surface Mounting Box

M200SMB-MM accommodates one Monitor Module

IM-10 or Control Module CR-6.

• ADM loop technology with

System Sensor/200 protocol

• 6 independent, dry relay outputs
• Status LED for each output
• Setting of module address via

decadic rotary switches

• Mounting in surface mounting box

Specifi cations

Operating voltage

Supply through loop voltage

Current consumption

approx. 1.5mA (quiescent)

Contact rating

2A/30VDC

Ambient temperature

0°C to +50°C

Dimensions L × W × H

172 Ч 147 Ч 25 (mm)

Weight

500g

Order number

249116

Order name

Control Module 6xRel.Out/Anal./200/SS CR-6

Surface Mounting Box

Ambient temperature

0°C to +50°C

Dimensions L × W × H

285 Ч 225 Ч 62 (mm)

Colour

cream

Weight

2kg

Order number

249117

Order name

Surface Mounting Box for Multimodule/SS M200SMB-MM