A

Building Safety. Building Security.

Permanent Connection

Specifi cations

A variety of peripheral devices can be connected to the

fi re detection control panel BC216-1S:

• Fire brigade key safe

• Fire brigade control unit

• Acoustic and optical signaling devices

• External protocol printer

• Remote indication unit

• Actuations

• Modules for remote parameterisation and remote

maintenance via computer newtork, modem or GSM

connection

– and much more.

Mains voltage

230VAC +10/-15%, 50Hz

Connection power

60VA

Output voltage

typ. 28VDC

Output peak current

max. 1.8A

Connection of external devices

typ. 0.8A, site-specifi c

Own current consumption at 24V

typ. 115mA (incl. LIF64-1, without detectors/modules)

Ambient temperature

-5°C to +50°C

Dimensions W × H × D

420 Ч 520 Ч 120 (mm)

Colour

gray-white, RAL 9002

Weight without accumulator

approx. 6kg

Approvals (EN 54-2, EN 54-4)

VdS G201017

FT 14/147/3/99 (Austria),

Order name

Fire detection control panel BC216-1S