beautypg.com

LST HT-11001 User Manual

Specifi cations

background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

HT-11001_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

• Addressable conventional technology
• Maximum temperature 57°C
• Individual detector addressing by

means of optional address module

• Optional connection of remote

indicator

• Extremely fl at design
• Sealed electronics

Description

The Thermal ROR Detector HT-11001 reacts to tempe-

rature changes within defi ned periods of time, up to a

maximum temperature of 57°C. The intelligent evaluati-

on of these data allows the early detection of spreading

fi res. The detector complies with Class A1R and can be

used up to a room height of 7.5m.

Addressable conventional technology is used for alarm

transmission to the fi re detection control panel. By

means of the optional Address Module NG60-1, each

detector can be addressed individually, thus allowing to

display the detector address, as well as an assigned

element text, on a suitable fi re detection control panel.

A detector fault is indicated by a yellow fl ashing of the

multicoloured status LED.

The detector can be attached to various bases and it

can be protected against theft.

Specifi cations

Operating voltage

Supply through the detector line voltage

Current consumption

typ. 65µA (quiescent)

Alarm temperature

57°C (maximum-heat component)

Operating temperature

max. +50°C

Ambient temperature

- 40°C to +70°C (no condensation or icing)

Relative humidity

0 – 98% (no condensation)

Dimensions ш Ч H

100 × 36 (mm)

Colour

white

Weight

70g

Approval

VdS G204033

Order number

242030

Order name