PIPING A HEATING - COOLING SYSTEM TO A WATER

BOILER AND CHILLER

Figure below illustrates a method of piping a heating-cooling

system to a water boiler and a chiller. Hand valves (shown) or

automatic valves must be installed to prevent circulation of

chilled water in the boiler or hot water in the chiller.

The air control system and pressure control system must

operate with chiller only, or the boiler only, being valved to the

piping system. Separate control devices on the boiler and

chiller may be used, or a single set of air and pressure con-

trols on the common piping may be preferred.

If the boiler is used to supply hot water to heating coils in air

handling units, flow control valves or other devices must be

installed to prevent gravity circulation of water in the coils dur-

ing the cooling cycle.

IF REPLACEMENT PARTS ARE NEEDED

When parts are needed, refer to boiler model and serial number

shown on the boiler name/rating plate. Refer to publication num-

ber V-10PL Victory Replacement Parts for part numbers. When-

ever possible refer to the original order by number

and date.

Control identification and replacement should not be attempted

by unskilled personnel. Only simple, easily-identified controls

and parts may be obtained locally. All other controls and parts

should be identified by and ordered from Slant/Fin. Relief/Safety

valves must be ASME rated for the pressure and gross output of

the boiler.