B. PUMP LOCATION-Locating low-head pump(s) on

return to boiler is acceptable for smaller boiler sizes in

residences of one or two stories. The alternate pump

location shown in illustration on page 11 is required in

large, multi-story building installations, especially when

high-head pumps are used. The compression tank

must be at the boiler or between boiler and supply

main pump(s).

C. On a hot water boiler installed above radiation level,

the boiler must be provided with a low water cutoff

device at the time of installation by the installer.

OPERATING INSTRUCTIONS, BASIC

I. FILLING AND VENTING WATER SYSTEMS

A. Fill the system with water. Vent or purge of air.

B. Fire the boiler as soon as possible (see following warn-

ing and instructions) and bring water temperature to at

least 180 degrees, while circulating water in the sys-

tem.

C. Vent air and add water as needed to achieve operating

pressure on boiler gauge. Pressure must be between

approximately 12 psi (cold water) and 25 psi at water

temperature setting of high limit control, for boilers

equipped with 30 psi relief valves. Boilers rated for a

higher pressure and equipped with a matching relief

valve may operate at a higher pressure, but no higher

than 5 psi below the relief valve opening pressure.

D. Check for and repair any leaks before placing system

in service.

BEFORE FIRING BOILER, make these checks:

1. System is full of water. Air is vented or purged.

2. Relief valve is installed in accordance with ASME

Boiler and Pressure Vessel Code, Section IV. Valve

opening is not closed or reduced in size.

3. Venting is installed according to instructions under

“FLUE GAS VENTING REQUIREMENTS”.

4. All wiring is completed, following applicable wiring

diagrams.

5. Using soap solution, check for gas leaks in all gas

piping from meter to boiler pilot and manifold.

DO NOT use open flame.

II. INITIAL START

Safe lighting and other performance criteria were met

when testing various gas manifold and control assemblies

used on the Victory Series Boilers under the ANSI

Z21.13- 1987 Standard.

Instructions

Follow the lighting instructions in this manual that apply to

the particular ignition system equipped on this boiler.

(Also, see figures on page 2 for location of gas manifold,

gas valve and control assembly.) These instructions are

also attached to the boiler.

SAFETY INFORMATION

For Your Safety Read Before Operating

WARNING: If you do not follow these instructions exactly,

a fire or explosion may result causing property damage,

personal injury or loss of life.

A. This appliance is equipped with an ignition device

which automatically lights the pilot. DO NOT try to

light the pilot by hand.

B. BEFORE OPERATING smell all around the appliance

area for gas. Be sure to smell next to the floor because

some gas is heavier than air and will settle on the

floor.

WHAT TO DO IF YOU SMELL GAS

DO NOT try to light any appliance.

DO NOT touch any electric switch; DO NOT use

any phone in your building.

Immediately call your gas supplier from a neighbor's

phone. Follow the gas supplier's instructions.

If you cannot reach your gas supplier, call the fire

department.

C. Use only your hand to push in or turn the gas control

knob. NEVER use tools. If the knob will not push in or

turn by hand, don't try to repair it, call a qualified ser-

vice technician. Force or attempted repair may result

in a fire or explosion.

D. DO NOT use this appliance if any part has been

underwater. Immediately call a qualified service tech-

nician to inspect the appliance and to replace any part

of the control system and any gas control which has

been underwater.

OPERATING INSTRUCTIONS

FOR VR8204 OR VR8304 VALVE

1. STOP! Read the safety information above.

2. Set the thermostat to lowest setting.

3. Turn off all electric power to the appliance.

4. This appliance is equipped with an ignition device

which automatically lights the pilot. DO NOT try to

light the pilot by hand.

5. Turn gas control knob clockwise to "OFF". DO

NOT force.

6. Wait five (5) minutes (longer for propane) to clear out

any gas, then smell for gas, including near the floor. If

you then smell gas, STOP! Follow "B" in the safety

information above. If you don't smell gas, go to next

step.

7. Turn gas control knob counterclockwise to "ON".

Figure 11.