Siemens SED2 User Manual
Page 26
SED2 AOP Operating Instructions
18
Siemens Building Technologies
1. From the main menu, use
and
to scroll through the list of options and to highlight the
Download item.
Press
to confirm the selection. Press
to cancel the download process.
The AOP displays a download menu.
NOTE:
In master mode, the AOP prompts for selection of a specific SED2 VFD from a
list of the networked SED2 VFDs.
2. Use and
to scroll through the list of parameter sets and to highlight the parameter set
from which information will be copied.
Press
to confirm the selection.
3. The AOP displays a confirmation screen.
Press
to confirm the selection. Press
to cancel the download process.
4. The AOP displays a wait screen while the download process occurs.
5. On completion of the download process, the AOP returns to the main menu.
NOTES:
If the download fails, perform the following:
1. Reset VFD parameters: Commissioning Parameter P0010=30 for factory settings and
Factory Reset Parameter P0970=1 to reset all parameters to their default values.
2. Cycle VFD power off/on.
3. Repeat the download process.