SED2 AOP Operating Instructions

8

Siemens Building Technologies

Quick Commissioning

NOTE:

Simultaneously press

and

, at any time, to display the main menu.

The following table describes the main menu items.

Menu Item

Description

Operate

Displays the current status of the SED2 VFD/motor.

Diagnostics

Displays a recent fault history.

Parameters

Allows you to select a parameter group (similar to Parameter Filter P0004) and to
configure individual parameters.

Mode

Allows you to select the AOP mode of operation as follows:

Local

Master

Internal

Slave

PC Mode

Upread
(upload)

Allows you to read a parameter set from a SED2 VFD to the AOP.

Download

Allows you to write a parameter set from the AOP to a SED2 VFD.

Language

Allows you to select a new language for the AOP display.

Setup

Allows you to customize the configuration of the AOP.

Timer

Allows you to set a start and stop time for SED2 VFD operation.

1.

Use

and

to scroll through the list of options and to highlight the Parameters item.

Press

to confirm the selection.


The AOP prompts to select the desired parameter group. Use

and

to scroll through the

list of options and to highlight the All parameters item. Press

to confirm the selection.

NOTE:

AOP Parameters, provides an overview of parameter access levels and a
procedure for editing parameters.

2.

Use

and

to scroll through the parameters and to highlight User Access Level P0003.

Press

to confirm the selection and the cursor advances to the parameter value.


Use

and

to set P0003=3 (Expert).

Press

to confirm the setting and the cursor returns to the parameter.

3.

Use

and

to scroll through the parameters and to highlight Commissioning Parameter

P0010. Press

to confirm the selection and the cursor advances to the parameter value.


Use

and

to set P0010=1 (Quick Commissioning).

Press

to confirm the setting and the cursor returns to the parameter.