beautypg.com

Siemens SED2 User Manual

Page 17

background image

AOP Start-Up & Initialization

Siemens Building Technologies, Inc.

9

4.

Use

and

to scroll through the parameters and to highlight Command Source P0700.

Press

to confirm the selection and the cursor advances to the parameter index.


Use

and

to scroll through the indexes for P0700 and to highlight P0700[1] (index 1).

Press

to confirm the selection and the cursor advances to the parameter value.


Use

and

to set P0700[1]=4 (USS on BOP/AOP local link).

Press

to confirm the setting and the cursor returns to the parameter.

5.

Use

and

to scroll through the parameters and to highlight Selection of Frequency

Setpoint P1000. Press

to confirm the selection and the cursor advances to the parameter

index.

Use

and

to scroll through the indexes for P1000 and to highlight P1000[1] (index 1).

Press

to confirm the selection and the cursor advances to the parameter value.


Use

and

to set P1000[1]=1 (motor potentiometer [MOP] setpoint).

Press

to confirm the setting and the cursor returns to the parameter.

6.

Use

and

to scroll through the parameters and to highlight Commissioning parameter

P0010. Press

to confirm the selection and the cursor advances to the parameter value.


Use

and

to set P0010[0]=0 (Ready) to exit the quick commissioning mode. Press

to confirm the setting and the cursor returns to the parameter.

7.

Use

and

to scroll through the parameters and to highlight USS Telegram Off Time

P2014. Press

to confirm the selection and the cursor advances to the parameter index.


Use

and

to scroll through the indexes for P2014 and to highlight P2014[1] (index 1,

Serial Interface BOP Link). Press

to confirm the selection and the cursor advances to the

parameter value.

Use

and

to set P2014[1]=5000 (USS on BOP/AOP local link) to prevent unexpected

drive operation. In this mode, removal of the AOP from the SED2 VFD causes a timeout to
occur in 5 seconds. Press

to confirm the setting and the cursor returns to the parameter.

8.

Press

to return to r0000. Press

to display the standard (operate) screen.

9.

Press

to switch the SED2 to hand mode.

10.

Press

to start the SED2.

11.

Use

to increase the output; Use

to decrease the output.