Voltage Conversion
The Model 1824 is prewired for a 220V power supply, but
it can be rewired to operate on a 110V power supply. To
reduce the risk of electrocution, machine damage, or an
electrical fire, this procedure must be performed by an
electrician or qualified service personnel. The procedure
involves moving terminal jumpers inside the motor
junction box, replacing the machine circuit breaker, and
replacing the plug on the power cord.
The require machine circuit breaker can be purchased
from an authorized Shop Fox dealer. The required
plug and receptacle can be purchased from your local
hardware store or it may be provided by your electrician.
Items Needed
Qty
Phillips Screwdriver #2 .........................................1
NEMA 5-20 Plug ..................................................1
Circuit Breaker 20A (Part No. X1824204-1) .................1
To convert the table saw to 110V, do these steps:
1. DISCONNECT TABLE SAW FROM POWER!
2. Open the motor junction box, then loosen the four
screws indicated in
Figure 4.
3. Remove the two center jumpers (they are stacked
together), reposition them as shown in
Figure 5,
then re-tighten the four screws loosened in
Step 2.
4. Close and secure the motor junction box.
5. Remove the START/STOP switch box from the switch
mounting plate.
6. Replace the pre-installed 10A circuit breaker
(see
Figure 6) with the 20A circuit breaker, then
re-install the switch box.
7. Replace the existing power cord plug with a NEMA
5-20 plug, according to the instructions and wiring
diagram provided by the plug manufacturer.
Load
Line
KEDU HY56
20A 250V
35A 125V
Neutral
Hot
Ground
110 VAC
5-20 Plug
(As Recommended)
110V/220V
MOTOR
SWITCH
BOX
Rewired for 110V
Motor Rewired
for 110V
Motor Prewired
for 220V
Start
Capacitor
200MFD
250VAC
Run
Capacitor
60MFD
300VAC
Circuit Breaker (10A at 220V) (20A at 110V) ON/OFF SWITCH Ground Hot Hot 6-20 PLUG 220 VAC Rewired for 110V Figure 4. Locations of screws to be loosened. Center Jumpers Loosen These Screws Load Line KEDU HY56 20A 250V 35A 125V Neutral Hot Ground 110 VAC 5-20 Plug (As Recommended) 110V/220V MOTOR SWITCH BOX Rewired for 110V Motor Rewired for 110V Motor Prewired for 220V Start Capacitor 200MFD 250VAC Run Capacitor 60MFD 300VAC Circuit Breaker (10A at 220V) (20A at 110V) ON/OFF SWITCH Ground Hot Hot 6-20 PLUG 220 VAC Rewired for 110V Figure 5. Relocated jumpers. New Jumper Locations Circuit Breaker Figure 6. Location of switch circuit breaker. This manual was current at the time of printing. However, if the motor wiring diagram provided on the inside of the junction box cover differs from this manual, always use the junction box cover wiring diagram. This should reflect any changes that may have occurred after printing.