Power Specifications
007-4857-002
157
Power Specifications
Table A-6 shows the power specifications for the system.
Heat dissipation
Altix 450
29.86 kBTU/hr maximum (based on 8.75 kW)
Cooling requirement
Ambient air cooling only
Air flow: intake (front),
exhaust (rear)
Approximately 750 CFM (normal operation)
Maximum altitude
10,000 ft. (3,049 m) operating
40,000 ft. (12,195 m) non-operating
Acoustical noise level
Less than 65 dBa maximum (with doors)
Table A-6
Power Specifications
Feature
Specification
Single-phase power requirements
Voltage
Frequency
Power
200-240V (180-254 VAC min/max)
50-60 Hz
17.5 kW max per tall rack
8.75 kW max per short rack
Hold-up time
16 ms
Total harmonic distortion
Less than 10% at full load
Table A-5
Environmental Specifications (20U Rack) (continued)
Feature
Specification