7: Troubleshooting and Diagnostics
Temperature messages: low alt.
ATTN:
temperature reached @ xxC xxF
The ambient temperature at the IRU’s air inlet has
exceeded 30
° C.
ATTN:
temperature reached @ xxC xxF
The ambient temperature at the IRU’s air inlet has
exceeded 35
°C.
ATTN:
reached @ xxC xxF
The ambient temperature at the IRU’s air inlet has
exceeded 40
°C.
Temperature messages: high alt.
ATTN:
temperature reached @ xxC xxF
The ambient temperature at the IRU’s air inlet has
exceeded 27
°C.
ATTN:
temperature reached @ xxC xxF
The ambient temperature at the IRU’s air inlet has
exceeded 31
°C.
ATTN:
reached @ xxC xxF
The ambient temperature at the IRU’s air inlet has
exceeded 35
°C.
Temperature stable message:
ATTN:
@ xxC/xxF
The ambient temperature at the IRU’s air inlet has
returned to an acceptable level.
Power-off messages:
Auto power down in xx seconds
The L1 controller has registered a fault and is
shutting down. The message displays every five
seconds until shutdown.
IRU appears to have been powered down
The L1 controller has registered a fault and has shut
down.
Table 7-2
L1 Controller Messages (continued)
L1 System Controller Message
Message Meaning and Action Needed