beautypg.com

Environmental specifications, Table a-4, Table a-5 – Intel SGI Altix 450 User Manual

Page 178

background image

156

007-4857-002

A: Technical Specifications and Pinouts

Environmental Specifications

Table A-4 lists the environmental specifications of the 42U rack system. Table A-5 provides the
environmental information for the 20U system.

.

Table A-4

Environmental Specifications (42U Rack)

Feature

Specification

Temperature tolerance
(operating)

+5

°C (41 °F) to +35

°C (95 °F) (up to 1500 m / 5000 ft.)

+5

°C (41

°F) to +30

°C (86

°F) (1500 m to 3000 m /5000 ft. to 10,000 ft.)

Temperature tolerance
(non-operating)

-40

°C (-40 °F) to +60

°C (140 °F)

Relative humidity

10% to 90% operating (no condensation)
8% to 95% non-operating (no condensation)

Heat dissipation

Altix 450 (42U rack)

59.71 kBTU/hr maximum (based on 17.5 kW)

Cooling requirement

Ambient air cooling

Air flow: intake (front),
exhaust (rear)

Approximately 1400 CFM (normal operation)

Maximum altitude

10,000 ft. (3,049 m) operating
40,000 ft. (12,195 m) non-operating

Acoustical noise level

Less than 65 dBa maximum (with doors)

Table A-5

Environmental Specifications (20U Rack)

Feature

Specification

Temperature tolerance
(operating)

+5

°C (41 °F) to +35

°C (95 °F) (up to 1500 m / 5000 ft.)

+5

°C (41

°F) to +30

°C (86

°F) (1500 m to 3000 m /5000 ft. to 10,000 ft.)

Temperature tolerance
(non-operating)

-40

°C (-40 °F) to +60

°C (140 °F)

Relative humidity

10% to 90% operating (no condensation)
8% to 95% non-operating (no condensation)