beautypg.com

6 environment, Table 1-3 ambient temperature and humidity, 5˚c to 40˚c – IBM DCS9550 1S1 User Manual

Page 26: 20% to 80, Non-condensing, 23˚c, 0˚c to +50˚c, 8% to 80, 27˚c, 1˚c to +60˚c

background image

Introduction

IBM System Storage DCS9550 1S1 Storage Expansion Unit Installation, Service, and User Guide

11

1.4.6

Environment

Table 1–3

Ambient Temperature and Humidity

Temperature Range

Relative Humidity

Max. Wet Bulb

Operational

5°C to 40°C

20% to 80%

non-condensing

23°C

Non-Operational

0°C to +50°C

8% to 80%

non-condensing

27°C

Storage

1°C to +60°C

8% to 80%

non-condensing

29°C

Shipping

-40°C to +60°C

5% to 100%

non-precipitating

29°C

Airflow

System must be operated with low pressure rear exhaust installation

(Back pressure created by rack doors and obstacles not to exceed

5 pascals [0.5mm Water gauge])

Altitude, Operational

0 to 2133 m (0 to 7,000ft)

(10,000ft at maximum ambient of 35°C)

Altitude, Non-Operational

-305 to 12,192m (-1000 to 40,000ft)

Shock, Operational

Vertical axis 5g peak 1/2 sine, 10ms

Shock, Non-Operational

30g 10ms 1/2 sine

Vibration, Operational

0.21grms 5-500 Hz Random

Vibration, Non-Operational

1.04grms 2-200 Hz Random

Vibration, Relocation

0.3g 2-200 Hz sine

Acoustics

Less than 6.0 LwA

Orientation & Mounting

19" Rack mount (3EIA Units)

• Rack Rails

To fit 800mm depth Racks compliant with IEC 297

• Rack Characteristics

Back pressure not exceeding 5 pascals (0.5mm water gauge)

Safety & Approvals

CE, UL, cUL