7-1. PERFORMANCE DATA
1) COOLING CAPACITY

Model

Indoor air

Outdoor intake air DB temperature (˚F)

IWB 75

85

95

105

115

(˚F)

TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC

MUZ-FD09NA

71

11.0

6.9

0.58 10.3

6.5

0.63

9.7

6.1

0.68

9.0

5.6

0.72

8.3

5.2

0.75

67

10.4

7.9

0.55

9.7

7.4

0.60

9.0

6.8

0.65

8.4

6.4

0.69

7.7

5.8

0.72

63

9.8

8.8

0.52

9.1

8.1

0.58

8.5

7.6

0.62

7.7

6.9

0.66

7.0

6.3

0.69

MUZ-FD12NA

71

14.7

8.8

0.85 13.7

8.2

0.94 12.9

7.7

1.01 12.0

7.2

1.06 11.0

6.6

1.10

67

13.9 10.2 0.81 13.0

9.5

0.89 12.0

8.8

0.96 11.2

8.1

1.02 10.3

7.5

1.07

63

13.1 11.3 0.77 12.1 10.5 0.85 11.3

9.7

0.92 10.3

8.9

0.98

9.4

8.1

1.02

NOTE

: 1. IWB : Intake air wet-bulb temperature

TC : Total Capacity (x10

3

Btu/h)

SHC : Sensible Heat Capacity (x10

3

Btu/h)

TPC : Total Power Consumption (kW)

2. SHC is based on 80˚F of indoor Intake air DB temperature.

2) COOLING CAPACITY CORRECTIONS

Refrigerant piping length (one way : ft.)

25 (std.)

40

65

MUZ-FD09NA
MUY-FD12NA

1.0

0.954

0.878

3) HEATING CAPACITY

Model

Indoor air

Outdoor intake air WB temperature (˚F)

IDB 15

25

35

43

45

55

(˚F) TC TPC TC TPC TC TPC TC TPC TC TPC TC TPC

MUZ-FD09NA

75

6.3

0.56

7.9

0.66

9.4

0.73

10.6

0.77

11.0

0.78

12.4

0.81

70

6.7

0.54

8.2

0.64

9.6

0.71

10.9

0.75

11.2

0.77

12.7

0.80

65

6.9

0.52

8.6

0.62

10.0

0.69

11.2

0.73

11.6

0.74

13.0

0.78

MUZ-FD12NA

75

7.9

0.73

9.9

0.86

11.8

0.96

13.3

1.00

13.7

1.02

15.5

1.06

70

8.4

0.71

10.2

0.84

12.0

0.93

13.6

0.98

14.0

1.00

15.8

1.04

65

8.6

0.68

10.7

0.81

12.4

0.91

14.0

0.96

14.4

0.97

16.2

1.02

NOTE

: 1. IDB : Intake air dry-bulb temperature

TC : Total Capacity (x10

3

Btu/h)

TPC : Total Power Consumption (kW)

2. Above data is for heating operation without any frost.

How to operate with fixed operational frequency of the compressor.

1. Press the EMERGENCY OPERATION switch on the front of the indoor unit, and select either EMERGENCY COOL

mode or EMERGENCY HEAT mode before starting to operate the air conditioner.

2. The compressor starts with operational frequency.

3. The fan speed of the indoor unit is High.

4. This operation continues for 30 minutes.

5. In order to release this operation, press the EMERGENCY OPERATION switch twice or once, or press any button on

the remote controller.