25

Is the thermistor normal? (Refer to 10-6.1.)

Reconnect the connector of thermistor.

Turn ON the power supply and press EMERGENCY OPERATION switch.

No

Replace the thermistor except RT64. When RT64 is

abnormal, replace the inverter P.C. board.

Does the unit operate for 10 minutes or more

without showing thermistor abnormality?

OK.

(Cause is poor contact.)

Replace the inverter P.C. board.

Thermistor

Symbol

Connector, Pin No.

Board

Defrost

RT61

Between CN641 pin1 and pin2

Inverter P.C. board

Discharge temperature

RT62

Between CN641 pin3 and pin4

Fin temperature

RT64

Between CN642 pin1 and pin2

Ambient temperature

RT65

Between CN643 pin1 and pin2

Outdoor heat exchanger temperature

RT68

Between CN644 pin1 and pin3

Yes

Yes

No

G Check of outdoor thermistors

H Check of R.V. coil

First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4.

In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector

although any signal is not being transmitted to R.V. coil.

Check if CN721 is connected.

Is there 230 VAC between CN721 and

on the inverter P.C. board 3 minutes

after the power supply is turned ON?

No

Yes

Replace the inverter

P.C. board.

Replace the 4-way valve.

Unit operates COOL mode even if it is set to HEAT mode.

Is there 230 VAC between CN721 and

on the inverter P.C. board 3 minutes

after the power supply is turned ON?

Yes

No

Replace the inverter

P.C. board.

Replace the 4-way valve.

Unit operates HEAT mode even if it is set to COOL mode.

Disconnect connector (CN61)

between the compressor and the

intelligent power module.

Turn ON the power supply and

press EMERGENCY OPERATION

switch twice (HEAT mode).

Disconnect connector (CN61)

between the compressor and the

intelligent power module.

Turn ON the power supply and

press EMERGENCY OPERATION

switch once (COOL mode).

Disconnect the connector of thermistor in the outdoor P.C. board (see

below table), and measure the resistance of thermistor.