Test condition – MITSUBISHI ELECTRIC MUZ-FD09NA- U1 User Manual

Page 5

background image

55

Test condition

ARI

Mode Test

Indoor air condition

Outdoor air condition

Dry bulb (°F)

Wet bulb (°F)

Dry bulb (°F)

Wet bulb (°F)

SEER

(Cooling)

"A" Cooling Steady State

at rated compressor Speed

80

67

95

(75)

"B-2" Cooling Steady State

at rated compressor Speed

80

67

82

(65)

"B-1" Cooling Steady State

at minimum compressor Speed

80

67

82

(65)

Low ambient Cooling Steady State

at minimum compressor Speed

80

67

67

(53.5)

Intermediate Cooling Steady State

at Intermediate compressor Speed 5

80

67

87

(69)

HSPF

(Heating)

Standard Rating-Heating

at rated compressor Speed

70

60

47

43

Low temperature Heating

at rated compressor Speed

70

60

17

15

Max temperature Heating

at minimum compressor Speed

70

60

62

56.5

High temperature Heating

at minimum compressor Speed

70

60

47

43

Frost Accumulation

at rated compressor Speed

70

60

35

33

Frost Accumulation

at Intermediate compressor Speed 5

70

60

35

33

5

: At Intermediate compressor Speed

= ("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".

3, 4

(2) OPERATION

Mode

Condition

Intake air temperature (°F)

Indoor

Outdoor

DB

WB

DB

WB

Cooling

Standard temperature

80

67

95

Maximum temperature

90

73

115

Minimum temperature

67

57

14

Maximum humidity

78 %

Heating

Standard temperature

70

60

47

43

Maximum temperature

80

67

75

65

Minimum temperature

70

60

14

13

OPERATING RANGE

(1) POWER SUPPLY

Rated voltage

Guaranteed Voltage

Outdoor unit

208/230 V

1 phase

60 Hz

Min.187 V

208 V

230 V Max.253 V