No. Symptom LED

indication Abnormal point/

Condition

Condition Correspondence

18

Outdoor unit

operates.

7-time fl ash

2.5 seconds OFF

Low discharge tem-

perature protection

Temperature of discharge temperature thermistor has been

122°F (50°C) or less for 20 minutes.

Refer to 10-5. "Check of LEV".

Check refrigerant circuit and refrig-

erant amount.

19

8-time fl ash

2.5 seconds OFF

PAM protection

PAM: Pulse Ampli-

tude Modulation

The overcurrent fl ows into IGBT (Insulated Gate Bipolar tran-

sistor : TR821) or the bus-bar voltage reaches 320 V or more,

PAM stops and restarts.

This is not malfunction. PAM protec-

tion will be activated in the following

cases;

1 Instantaneous power voltage drop

(Short time power failure)

2 When the power supply voltage is

high.

20

9-time fl ash

2.5 seconds OFF

Inverter check mode The connector of compressor is disconnected, inverter check

mode starts.

Check if the connector of the com-

pressor is correctly connected.

Refer to 10-5. "How to check in-

verter/compressor".