ACTUATOR CONTROL

MUZ-FD09NA MUZ-FD12NA

8-2. R.V. COIL CONTROL

Heating . . . . . . . . . . . . . . . . . ON

Cooling . . . . . . . . . . . . . . . . . OFF

Dry . . . . . . . . . . . . . . . . . . . . OFF

NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.

ON

OFF

ON

OFF

Outdoor fan

motor

Compressor

5 seconds

15 seconds

8-1. OUTDOOR FAN MOTOR CONTROL

The fan motor turns ON/OFF, interlocking with the compressor.

[ON] The fan motor turns ON 5 seconds before the compressor starts up.

[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.

8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR

Sensor Purpose

Actuator

Compressor

LEV

Outdoor

fan motor

R.V. coil Indoor fan

motor

Discharge temperature thermistor

Protection

Indoor coil temperature thermistor

Cooling : Coil frost prevention

Heating : High pressure protection

Defrost thermistor

Cooling : High pressure protection

Heating : Defrosting

Fin temperature thermistor

Protection

Outdoor heat exchanger temperature thermistor

High pressure protection

Ambient temperature thermistor

Low ambient temperature operation

ON

OFF

Compressor

Outdoor fan

motor

R.V.coil

ON

OFF

ON

OFF

5 seconds

5 seconds