10-3. TROUBLESHOOTING CHECK TABLE

No. Symptom LED

indication Abnormal point/

Condition

Condition Correspondence

1

Outdoor unit

does not oper-

ate.

1-time fl ash every

2.5 seconds

Outdoor power sys-

tem

Overcurrent protection stop is continuously performed 3 times

within 1 minute after the compressor gets started, or failure of

restart of compressor has repeated 24 times.

Reconnect connector of compres-

sor.

Refer to 10-5. "How to check in-

verter/compressor".

Check stop valve.

2

Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,

defrost thermistor, P.C. board temperature thermistor or ambi-

ent temperature thermistor shorts or opens during compressor

running.

Refer to 10-5. "Check of outdoor

thermistors".

3

Outdoor control sys-

tem

Nonvolatile memory data cannot be read properly.

(POWER lamp of the indoor unit lights up or fl ashes 7 times.)

Replace inverter P.C. board.

4

6-time fl ash

2.5 seconds OFF

Serial signal

The communication fails between the indoor and outdoor unit

for 3 minutes.

Refer to 10-5. "How to check

miswiring and serial signal error.

5

11-time fl ash

2.5 seconds OFF

Stop valve/

Closed valve

Closed valve is detected by compressor current.

Check stop valve.

6

14-time fl ash

2.5 seconds OFF

Outdoor unit

(Other abnormality)

Outdoor unit is defective.

Refer to 10-2.2. "Flow chart of the

detailed outdoor unit failure mode

recall function".

7

'Outdoor unit

stops and

restarts 3 min-

utes later' is

repeated.

2-time fl ash

2.5 seconds OFF

Overcurrent protec-

tion

Large current fl ows into intelligent power module.

When overcurrent protection occurs within 10 seconds after

compressor starts, compressor restarts after 15 seconds.

Reconnect connector of compres-

sor.

Refer to 10-5. "How to check in-

verter/compressor".

Check stop valve.

8

3-time fl ash

2.5 seconds OFF

Discharge tempera-

ture overheat protec-

tion

Temperature of discharge temperature thermistor exceeds 241

°F (116°C), compressor stops. Compressor can restart if dis-

charge temperature thermistor reads 212°F (100°C) or less 3

minutes later.

Check refrigerant circuit and refrig-

erant amount.

Refer to 10-5. "Check of LEV".

9

4-time fl ash

2.5 seconds OFF

Fin temperature

/P.C. board tem-

perature thermistor

overheat protection

Temperature of fi n temperature thermistor on the heat sink

exceeds 167 ~ 176°F (75 ~ 80°C) or temperature of P.C. board

temperature thermistor on the inverter P.C. board exceeds 158

~ 167°F (70 ~ 75°C).

Check around outdoor unit.

Check outdoor unit air passage.

Refer to 10-5. "Check of outdoor

fan motor".

10

5-time fl ash

2.5 seconds OFF

High pressure pro-

tection

Indoor coil thermistor exceeds 158°F (70°C) in HEAT mode.

Defrost thermistor exceeds 158°F (70°C) in COOL mode.

Check refrigerant circuit and refrig-

erant amount.

Check stop valve.

11

8-time fl ash

2.5 seconds OFF

Compressor syn-

chronous abnormal-

ity

The waveform of compressor current is distorted.

Reconnect connector of compres-

sor.

Refer to 10-5. "How to check in-

verter/compressor".

12

10-time fl ash

2.5 seconds OFF

Outdoor fan motor

Outdoor fan has stopped 3 times in a row within 30 seconds

after outdoor fan start-up.

Refer to 10-5. "Check of outdoor

fan motor.

Refer to 10-5. "Check of inverter

P.C. board.

13

12-time fl ash

2.5 seconds OFF

Each phase current

of compressor

Each phase current of compressor cannot be detected nor-

mally.

Refer to 10-5. "How to check in-

verter/compressor".

14

13-time fl ash

2.5 seconds OFF

DC voltage

DC voltage of inverter cannot be detected normally.

Refer to 10-5. "How to check in-

verter/compressor".

15 Outdoor unit

operates.

1-time fl ash

2.5 seconds OFF

Frequency drop by

current protection

Current from power outlet is nearing Max. fuse size.

The unit is normal, but check the

following.

Check if indoor fi lters are clogged.

Check if refrigerant is short.

Check if indoor/outdoor unit air cir-

culation is short cycled.

16

3-time fl ash

2.5 seconds OFF

Frequency drop by

high pressure pro-

tection

Temperature of indoor coil thermistor exceeds 131°F (55°C) in

HEAT mode, compressor frequency lowers.

Frequency drop by

defrosting in COOL

mode

Indoor coil thermistor reads 46°F (8°C) or less in COOL mode,

compressor frequency lowers.

17

4-time fl ash

2.5 seconds OFF

Frequency drop by

discharge tempera-

ture protection

Temperature of discharge temperature thermistor exceeds 232

°F (111°C), compressor frequency lowers.

Check refrigerant circuit and refrig-

erant amount.

Refer to 10-5. "Check of LEV".

Refer to 10-5. "Check of outdoor

thermistors".

NOTE

: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.

2. LED is lighted during normal operation.

The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. Flashing

(Example) When the fl ashing frequency is “2”.

ON

OFF

2.5-second OFF

2.5-second OFF

0.5-second ON

0.5-second ON

LED

Flashing →

Inverter P.C. board (Parts side)