Instructions for the Installer

4.7.3 Malfunctions (or Problems) without Indications

This section gives an overview of the malfunctions (or problems) that are not displayed on the CC Ease display.

Problem/Malfunction

e

r

u

s

a

e

m

/

k

c

e

h

C

e

s

u

a

C

All OFF

Supply voltage

Check the fuse on the PCB panel.

• If the fuse is OK, the circuit board is defec-

tive.

.

d

e

li

a

f

s

a

h

y

l

p

p

u

s

r

e

w

o

p

s

n

i

a

m

e

h

T

e

g

a

tl

o

v

y

l

p

p

u

s

o

N

High air delivery tem-
perature in summer

Bypass remains closed

Lower
the comfort temperature.

Low air delivery tem-
perature in winter

Bypass remains open

Increase
the comfort temperature.

No or insuffi cient air
supply, shower re-
mains wet

Filter clogged

Replace
the fi lters.

Valves clogged

Clean
the valves.

Heat exchanger clogged by dirt.

Clean
the heat exchanger.

Heat exchanger frozen

Thaw
the heat exchanger.

Fan dirty

Clean
the fan.

Ventilation ducts clogged

Clean
the ventilation ducts.

MTD-ERV 350 in frost mode

Too noisy

Fan bearings defective

Replace
the fan bearings.

Fan settings

Change
the ventilation control settings.

Scraping noise

• Siphon is empty
• Siphon does not seal

Install
the siphon again.

Whistling noise

• An air leak somewhere in the system

Seal
the air leak.

Air fl ow noises

• Valves do not seal against duct.
• Valves not suffi ciently open

Install
the valves again.
Set
the valves again.

Leaking condensation Condensation drain clogged

Clean
the condensation drain.

Condensation from exhaust duct does not
run into drain plate

Check whether
the connections are correct.

Wired 3-position
switch does not func-
tion

Wiring is not OK

Check the circuitry of the 3-position switch
using a voltmeter:

• Voltage only on N & L3:

[The fans run at position 1].

• Voltage only on N & L3 & L2:

[The fans run at position 2].

• Voltage only on N & L3 & L1 or N & L3 & L2

& L1:
[The fans run at position 3].

Switch is defective

Wireless 3-position
switch does not func-
tion

Battery is discharged

Check
the battery.

Replace the battery, if necessary.

This manual is related to the following products: