4

31

Instructions for the Installer

Menu P5 ! Setting additional control functions

Values for additional control functions

d

r

a

d

n

a

t

S

m

u

m

i

x

a

M

m

u

m

i

n

i

M

n

o

i

t

p

i

r

c

s

e

D

u

n

e

m

-

b

u

S

P50

Activation of
the chimney sweep control system.

0 (= No)

1 (= Yes)

0

P51

Indicate whether
preheater is installed.

0 (= No)

1 (= Yes)

0

Note:
change only if a preheater was subsequently installed.
If the MTD-ERV 350 has to be reset to the works settings via P75, a subsequently installed
preheater will be reset as standard to "A

BSENT

".

Check the presence of the preheater after a general reset via menu P75.

P52

Setting the
preheater control.

v

Particularly safe setting.

v

Safe setting.

v

Nominal setting.

v

Economy setting.

0

3

2

Note:
The

PREHEATERISSWITCHEDONEARLIESTWITHTHE

particularlysafesetting.Thislevelthusoffersthe

greatest safety for maintaining balanced ventilation. On the other hand, the preheater is
switchedonthelatestinthe

ECONOMYSETTING

.Thislevelthusofferstheleastsafetyformaintain-

ing balanced ventilation.
During commissioning of the MTD-ERV 350 the preheater control can generally be left on
Level 2:N

OMINAL SETTING

(= works setting).Only in areas with cold winters (with daytime tem-

peraturesregularlyapprox.-10°Corbelow)shouldLevel1:

SAFESETTING

orevenLevel0:

PARTICU

-

LARLY SAFE SETTINGS

be selected.

Values for additional control functions

d

r

a

d

n

a

t

S

m

u

m

i

x

a

M

m

u

m

i

n

i

M

n

o

i

t

p

i

r

c

s

e

D

u

n

e

m

-

b

u

S

P53

Indicate presence of an extractor hood.

Note:
If an extractor hood is connected to the
ventilation system, the user can set the
ventilation levels for the extractor hood
via P29.

0 (= No)

1 (= Yes)

0

P54

Indicate presence of a bypass.

Note:
The MTD-ERV 350 is equipped with a by-
pass as standard. The value can therefore
be left at '1'.

0 (= No)

1 (= Yes)

1

P55

Indicate presence of a post-heater.

0 (= No)

1 (= Yes)

0

P56

Setting the necessary air volume for the
dwelling.
• nL: "Normal air volume".
• HL: "High air volume".

nL

HL

nL

Note:
Setting the air volume in P56 (to "nL" or "HL") forms the basis for setting the air specifi cations
and hence for setting the fans. For further information, see section 4.5 and P30 to P37.