beautypg.com

Menu p3 ! set ventilation controls, Menu p4 ! read off the temperatures (% and ppm) – MTD -ERV 350 User Manual

Page 34

background image

4

30 Instructions for the Installer

Menu P3 ! Set ventilation controls

Values for ventilation controls

Sub-menu

Description

Minimum

Maximum

Standard

P30

Setting the power (in %) of the exhaust air
fan in position "Absent".

0%

97%

Normal / High
15% / 15%

P31

Setting the power (in %) of the exhaust air
fan in position "Low".

16%

98%

Normal / High
35% / 40%

P32

Setting the power (in %) of the exhaust air
fan in position "Medium".

17%

99%

Normal / High
50% / 70%

P33

Setting the power (in %) of the exhaust air
fan in position "High".

18%

100%

Normal / High
70% / 90%

P34

Setting the power (in %) of the supply air
fan in position "Absent".

0%

97%

Normal / High
15% / 15%

P35

Setting the power (in %) of the supply air
fan in position "Low".

16%

98%

Normal / High
35% / 40%

P36

Setting the power (in %) of the supply air
fan in position "Medium".

17%

99%

Normal / High
50% / 70%

P37

Setting the power (in %) of the supply air
fan in position "High".

18%

100%

Normal / High
70% / 90%

P38

Current power (in %) of the exhaust air
fan.

-

-

Current %

P39

Current power (in %)
of the supply air fan.

-

-

Current %

Menu P4 ! Read off the temperatures (% and ppm)

Read off the temperatures (% and ppm)

Sub-menu

Description

Minimum

Maximum

Standard

P40

Current value of T

POST

-

HEATER

-

-

Current

o

C

P41

Comfort temperature

12

o

C

28

o

C

20

o

C

P42

Current value CO

2

-

-

Current ppm

P43

Current value relative humidity.

-

-

Current %

P44

Current value of T

EXTRACTOR

HOOD

-

-

Current

o

C

P45

Current value of T1
(= temperature of the outside air)

-

-

Current

o

C

P46

Current value of T2
(= temperature of the supply air)

-

-

Current

o

C

P47

Current value of T3
(= temperature of the exhaust air)

Current

o

C

P48

Current value of T4
(= temperature of the stale air)

Current

o

C

P49

Current value of T

GHE

(= temperature of the outside air for geo-
thermal heat exchanger)

Current

o

C

This manual is related to the following products: