LERT
MODULE
NUMBER
> @ <
METER
SERIAL
NUMBER
> — for example,
Alert3@PK-9910A010-00. This register will have to be altered in cases where
the receiving SMTP server only accepts emails from valid Internet domains
(i.e. SomeName.COM). This string may be up to 80 characters long.
5.
Click Send and save. When the Trigger input is pulsed, the Alert module
establishes communications with the SMTP mail server, and emails the alert
message.
Configuring the MeterM@il Feature to Send Data Logs
The Log Export module can send data logs in different ways, though only email is
currently implemented. This section discusses the ION modules involved in a
“data push” framework, plus the corresponding setup registers that you need to
configure in order to utilize the MeterM@il feature in the framework. The term
“data push” refers to the action of the Log Export module sending data logs. A
complete description of the Log Export module and the other ION modules
involved in the framework can be found in the online ION Programmer’s Reference
at www.pwrm.com.
The MeterM@il feature requires that an additional framework be created in Designer
before you can configure your meter to use the Log Export feature. Each “data push”
framework includes the following:
A Data Recorder module that records the values in its Source inputs each time it
is pulsed and stores these values in its Data Log output register.
A Log Export module that retrieves information from the Data Recorder
module’s Data Log register and sends the data to a specified destination.
A module that sends values to the Data Recorder module (e.g. Power Meter
module or a Modbus Import module).
A Periodic Timer module that triggers the Data Recorder module to record the
values it is sent.
A module that triggers the Log Export module to send the logged data (e.g. a
Clock or Periodic Timer module). This module is optional, because the Data
Recorder module’s Record Complete output register can be configured to trigger
the Log Export module to send data logs. When this is the case, the data logs are
emailed at the same interval that the Data Recorder module records new data.